AIR COOLED PRODUCTS:
Air-cooled chillers are required when no source of water
is available for cooling the condenser. These units use fans
to dissipate the heat removed by the refrigeration system.
When cooling requirements begin to exceed 24,000 Btu/Hr
(2 ton), the heat being dissipated into a room becomes a
concern. At that point we generally suggest either a water-cooled
chiller or an outdoor
air-cooled chiller.
Mydax Air-Cooled chillers are most often
recommended when one or more of the following are required:
|
|
|
precision temperature stability
|
|
|
special custom controls
|
|
|
special fluid handling (materials,
pumps, filtration)
|
|
high reliability |
|
both heating and cooling |
This product is available in the following
configurations:
|
| |
- Multi-Loop: 1, 2, and 3 independent channels
|
| |
|
Special Heat Transfer Fluid (HTF) could
be:
|
| |
|
| |
- Fluorinert and Novec fluids by 3M
|
| |
- Deionized Water, specify conductivity|resistivity
|
| |
|
| |
- International Space Station Fluid (ISS)
|
| |
|
|
|
| |
|
|
| |
In the Chart below, click on any of the models to see
a summary of the specifications. From there, you'll be
able to download the corresponding PDF datasheet
to a new window (approx. 1Mb in size, each).
|
|
| |
|
|
| |
|
|
| |
AIR-COOLED SERIES - PRODUCT
SUMMARY:
1M2A Specs
:
|
|
|
| Temperature Range |
+10°C to +20°C
|
| Number of Channels |
1 |
| Cooling Capacity |
586 Watts (2,000 Btu/Hr) @ +10°C fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
Deuterium Oxide / Methanol |
| Reservoir Volume |
1 Gallon |
| Pump: Flow at Pressure |
1 GPM at 120 PSI |
| Input Power |
208-240V, 60Hz, 20 Amp, Single-phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1M3A Specs :
|
[PDF
Datasheet] |
|
| Temperature Range |
+15°C to +40°C (+60°F to
+104°F)
|
| Number of Channels |
1 |
| Cooling Capacity |
1,000 Watts (3,415 Btu/Hr) @ +18°C fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
3M Fluorinert FC-77 |
| Reservoir Volume |
2 Gallons |
| Pump: Flow at Pressure |
1 GPM at 60 PSI |
| Input Power |
208-240V, 60Hz, 20 Amp, Single-phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
2M3A Specs :
|
[PDF
Datasheet] |
|
| Temperature Range |
+15°C to +60°C
|
| Number of Channels |
2 |
| Cooling Capacity, each |
500 Watts (1,700 Btu/Hr) @ +15°C
fluid
|
| Heating Capacity, each |
1,000 Watts
|
| Fluid (HTF) |
Deionized Water, 2M Ohm |
| Reservoir Volume, each |
1.8 Gallons |
| Pump: Flow at Pressure |
2 GPM at 50 PSI, each |
| Input Power |
208-230V, 60Hz, 20 Amp, single-phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
3M5A-SMQ Specs :
|
[PDF
Datasheet] |
|
| Temperature Range |
+15°C to +80°C
|
| Number of Channels |
3 |
| Cooling Capacity, each |
500 Watts (1,700 Btu/Hr) @ +15°C
fluid
|
| Heating Capacity,each |
500 Watts
|
| Fluid (HTF) |
Light Mineral Oil, 5W to 10W |
| Reservoir Volume, each |
1.8 Gallons |
| Pump: Flow at Pressure |
2 GPM at 70 PSI |
| Input Power |
208-240V, 60Hz, 20 Amp, Single-phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1M10A Specs
:
|
[PDF
Datasheet] |
|
| Temperature Range |
+10°C to +50°C
|
| Number of Channels |
1 |
| Cooling Capacity |
3,000 Watts (10,000 Btu/Hr) @ +12°C fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
3M Fluorinert FC-77 |
| Reservoir Volume |
10 Gallons |
| Pump: Flow at Pressure |
6 GPM at 20 PSI |
| Input Power |
208-240V, 60Hz, 25 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1M11A-ISS Specs
:
|
n/a |
|
| Temperature Range |
+15°C to +25°C
|
| Number of Channels |
1 |
| Cooling Capacity |
3,225 Watts (11,000 Btu/Hr) @ +20°C
fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
ISS Heat Transport Fluid |
| Reservoir Volume |
7 Gallons |
| Pump: Flow at Pressure |
2 GPM at 100 PSI |
| Input Power |
208-240V, 60Hz, 25 Amp, single-phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
2H12A-SS Specs
:
|
[PDF
Datasheet] |
|
| Temperature Range |
[A] -20°C to +80°C, [B]
+10°C to +80°C
|
| Number of Channels |
2 [A], [ B] |
| Cooling Capacity |
[A] 750W @ -20°C, [B] 2250 Watts @ +20°C
|
| Heating Capacity |
2,200 Watts, each
|
| Fluid (HTF) |
50/50 Ethylene Glycol/DI-Water |
| Reservoir Volume |
4 Gallons, each |
| Pump: Flow at Pressure |
3 GPM at 50 PSI, each |
| Input Power |
208-230V, 60Hz, 30 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1LH14A Specs :
|
[PDF
Datasheet] |
|
| Temperature Range |
-15°C to +50°C
(+5°F to +122°F)
|
| Number of Channels |
1 |
| Cooling Capacity |
4,100 Watts (14,000 Btu/Hr) @ -15°C
fluid
|
| Heating Capacity |
2,000 Watts
|
| Fluid (HTF) |
60/40 Ethylene Glycol/Water |
| Reservoir Volume |
30 Gallons |
| Pump: Flow at Pressure |
15 GPM at 30 PSI |
| Input Power |
208-240V, 60Hz, 50 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
2H14A Specs
:
|
[PDF
Datasheet] |
|
| Temperature Range |
+5°C to +90°C
|
| Number of Channels |
2 |
| Cooling Capacity, each |
4,100 Watts (14,000 Btu/Hr) @ +20°C
fluid
|
| Heating Capacity, each |
3,000 Watts
|
| Fluid (HTF) |
50/50 Ethylene Glycol/Water |
| Reservoir Volume, each |
4 Gallons |
| Pump: Flow at Pressure |
2 GPM at 60 PSI, each |
| Input Power |
208-230V, 60Hz, 30 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1M33A Specs
:
|
[PDF
Datasheet] |
|
| Temperature Range |
+15°C to +25°C (+59°F
to +77°F)
|
| Number of Channels |
1 |
| Cooling Capacity |
9,700 Watts (33,000 Btu/Hr) @ +20°C fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
Deionized Water, maintained 1.5 to 2M Ohm |
| Reservoir Volume |
16 Gallons |
| Pump: Flow at Pressure |
6 GPM at 100 PSI |
| Input Power |
208-240V, 60Hz, 30 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
1M90A Specs
:
|
[PDF
Datasheet] |
|
| Temperature Range |
+0°C to +20°C (+32°F
to +68°F)
|
| Number of Channels |
1 |
| Cooling Capacity |
26,400 Watts (90,000 Btu/Hr) @ +5°C fluid
|
| Heating Capacity |
-
|
| Fluid (HTF) |
Ethylene Glycol/Water |
| Reservoir Volume |
59 Gallons |
| Pump: Flow at Pressure |
30 GPM at 30 PSI |
| Input Power |
440/480V, 60Hz, 30 Amp, 3 phase |
| Configuration |
Indoor, Air-cooled |
| |
|
| |
|
|
|
| |

Advanced Temperature Control Technology

|
home |
support |
applications |
products |
sales|
contact
|
|
|