MYDAX AIR COOLED CHILLER / COOLER / HEATER PRODUCTS:
Air-cooled chillers are required when no source of water
is available for cooling the condenser. These units use fans
to dissipate the heat removed by the refrigeration system.
When cooling requirements begin to exceed 24,000 Btu/Hr
(2 ton), the heat being dissipated into a room becomes a
concern. At that point we generally suggest either a water-cooled
chiller or an outdoor
air-cooled chiller.
Mydax Air-Cooled chillers are most often
recommended when one or more of the following are required:
|
|
Precision temperature stability |
|
|
|
Multi Channel Systems for smaller footprint and economical solution for multiple cooling loop applications! |
|
Special fluid handling (materials,
pumps, filtration) |
|
High reliability |
|
Both heating and cooling |
This product is available in the following
configurations:
|
|
- Multi-Loop: 1, 2, 3 or more independent channels
|
|
|
Special Heat Transfer Fluid (HTF) could
be:
|
|
-
Galden and H-Galden by Solvay Solexis
(Ausimont)
|
|
- Fluorinert and Novec fluids by 3M
|
|
- Deionized Water, specify conductivity|resistivity
|
|
|
|
- International Space Station Fluid (ISS)
|
|
|
|
| |
|
|
| |
In the Chart below, click on any of the models to see a summary of the specifications. From there, you'll be able to download the corresponding PDF datasheet to a new window.
Please Note: These are example systems that can be customized to meet your specific needs.
|
|
| |
|
|
| |
|
|
| |
AIR-COOLED SERIES - PRODUCT
SUMMARY:
1M2A Specs
:
|
|
|
Temperature Range |
+10°C to +20°C |
Number of Channels |
1 |
Cooling Capacity |
586 Watts at +10°C
|
Heating Capacity |
-
|
Temperature Stability |
± 0.4°C or better |
Fluid (HTF) |
Deuterium Oxide / Methanol |
Reservoir Volume |
1 Gallon |
Pump: Flow at Pressure |
1 GPM at 120 PSI |
Input Power |
208/240VAC, 60Hz, 1ph, 20 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
1M6A Specs :
|
|
|
Temperature Range |
0°C to +60°C |
Number of Channels |
1 |
Cooling Capacity |
1.8 KW at +10°C (60Hz)
|
|
1.5 KW at +10°C (50Hz) |
Heating Capacity |
1.5 KW
|
Fluid (HTF) |
Fluorinert FC-3283 |
Temperature Stability |
± 0.5°C or better |
Reservoir Volume |
2.5 Gallons |
Pump: Flow at Pressure |
2.5 GPM at 50 PSI |
Input Power |
200/240VAC, 50/60Hz, 1ph, 25 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
2M8A Specs :
|
|
|
Temperature Range |
+15°C to +35°C |
Number of Channels |
2 |
Cooling Capacity |
885 Watts @ +28°C
(Loop 1)
|
|
1465 Watts @ +28°C (Loop 1) |
Heating Capacity |
2 KW each Loop
|
Temperature Stability |
± 1.0 °C or better |
Fluid (HTF) |
Water / Ethylene Glycol |
Reservoir Volume |
5 Gallons (Loop 1 Closed Loop) |
|
None (Loop 2 Open Loop) |
Pump: Flow at Pressure |
4 GPM at 30 PSI, 2 GPM at 60 PSI, each |
Input Power |
208/230VAC, 60Hz, 3ph, 40 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
2H12A-SS Specs :
|
|
|
Temperature Range |
-20°C to +80°C (Loop 1) |
|
+10°C to +80°C (Loop 2) |
Number of Channels |
2 |
Cooling Capacity |
750 Watts at -20°C (Loop 1)
|
|
2250 Watts at +20°C (Loop 2) |
Heating Capacity |
2.2 KW each loop
|
Temperature Stability |
± 0.25°C or better |
Fluid (HTF) |
DI Water / Ethylene Glycol |
Reservoir Volume, each |
4 Gallons |
Pump: Flow at Pressure |
3 GPM at 50 PSI |
Input Power |
208/230VAC, 60Hz, 3ph, 30 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
1M12A Specs
:
|
|
|
Temperature Range |
0°C to +60°C |
Number of Channels |
1 |
Cooling Capacity |
3.6 KW at +10°C (60Hz) |
|
3.0 KW at +10°C (50Hz) |
Heating Capacity |
3.0 KW |
Temperature Stability |
± 0.5°C or better |
Fluid (HTF) |
Fluorinert FC-3283 |
Reservoir Volume |
5 Gallons |
Pump: Flow at Pressure |
4 GPM at 50 PSI |
Input Power |
200/240VAC, 50/60Hz, 1ph, 40 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
1M75A Specs
:
|
|
|
Temperature Range |
+15°C to +40°C |
Number of Channels |
1 |
Cooling Capacity |
22 KW +21°C
fluid
|
Heating Capacity |
10 KW
|
Temperature Stability |
± 0.5°C or better |
Fluid (HTF) |
Water |
Reservoir Volume |
10 Gallons |
Pump: Flow at Pressure |
10 GPM at 25 PSI |
Input Power |
440/480VAC, 60 Hz, 3ph,
50 amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
1M90A Specs
:
|
|
|
Temperature Range |
+0°C to +20°C |
Number of Channels |
1 |
Cooling Capacity |
26 KW at +5°C
|
Heating Capacity |
-
|
Temperature Stability |
± 0.5°C or better |
Fluid (HTF) |
Ethylene Glycol / Water |
Reservoir Volume |
59 Gallons |
Pump: Flow at Pressure |
30 GPM at 30 PSI |
Input Power |
440/480VAC, 60Hz, 3ph, 30 Amp |
Configuration |
Indoor, Air-cooled |
|
|
|
|
|
|
| |

Advanced Temperature Control Technology

|