Mydax recirculating liquid chillers: About us, News, Frequently Asked Questions, Contact usTECHNICAL SERVICE SUPPORT for Mydax Chillers: Service-Warranty Options, Technical InformationAPPLICATIONS for Mydax Chillers: Pharmaceutical, Semiconductor, Aerospace, Automotive, Medical, Laser, Industrial, Biotech, Cryogenic. Prototype, Custom, OEM.Mydax PRODUCTS Chiller:  Very Low Temperature, Wide Temperature, Outdoor Air Cooled, Air Cooled, Water Cooled, Liquid to Liquid or Air Heat Exchanger, Precision Air Conditioner, Custom, Deionization Chelating FiltersSALES Mydax chillers: Design your Chiller, Computer Control, Engineering, Request a Quote
 
home | email 
Products
VLH Wide Temp
Outdoor Rated
Air-Cooled
Water-Cooled
Heat Exchangers
Precision Air
Extreme Custom
Multi-Channel
Filters

 

NON-REFRIGERATED, HEAT EXCHANGER PRODUCTS:

These Heat Exchangers are used when a source of building chiller water or facilities water is already available AND it is at least 5°C colder than your desired coolant temperature.

They provide a closed-loop recirculation system with a clean or pure fluid (like deionized water), and far superior temperature stability.

Read more in our description of the: Heat Exchanger Functional Description.

Mydax Heat Exchangers are most commonly recommended when one or more of the following are required:
precision temperature stability
special custom controls
special fluid handling (materials, pumps, filtration)
high reliability
both heating and cooling

This product is available in the following configurations:
 
  • Multi-Loop: 1, 2, and 3 independent channels
   
Special Heat Transfer Fluid (HTF) could be:
 
  • Deionized Water, specify conductivity|resistivity
 
  • Water/Dexcool or Ethylene Glycol 50/50
 
  • PAO, Royco 602; MIL-PRF-87252
 
  • Galden and H-Galden by Solvay Solexis (Ausimont)
 
  • Fluorinert and Novec fluids by 3M
   
 
 
 
 

In the Chart below, click on any of the models to see a summary of the specifications. From there, you'll be able to download the corresponding PDF datasheet to a new window (approx. 1Mb in size, each).

 
   
 
 
 

HEAT EXCHANGER SERIES - PRODUCT SUMMARY:

1HE20WA Specs :
Temperature Range
+15°C to +30°C
Number of Channels 1
Cooling Capacity

5,856 Watts (20,000 Btu/Hr) @ +5°C deltaT

Heating Capacity

-

Fluid (HTF) Deionized Water
Optional:
PAO
Reservoir Volume 6 Gallon
Pump: Flow at Pressure 5 GPM at 60 PSI
Input Power 208-240V, 60Hz, 15 Amp, single-phase
Configuration Indoor, Non-Refrigerated, Water-cooled
   
   
1HE222WB Specs :
 
Temperature Range
+10°C to +30°C
Number of Channels 1
Cooling Capacity

65,000 Watts (222,000 Btu/Hr) @ +4°C deltaT

Heating Capacity

-

Fluid (HTF) Deionized Water
Reservoir Volume 6 Gallons
Pump: Flow at Pressure 10 GPM at 60 PSI
Input Power 208-240V, 60Hz, 15 Amp
Configuration Indoor, Non-Refrigerated, Water-cooled
   
   
1HE240W Specs :
 
Temperature Range
+12°C to +25°C
Number of Channels 1
Cooling Capacity

70,275 Watts (240,000 Btu/Hr) @ +7.2°C (13°F) deltaT

Heating Capacity

-

Fluid (HTF) High Resistivity Deionized Water (1M-3M Ohm)
Reservoir Volume 42 Gallons
Pump: Flow at Pressure 60 GPM at 60 PSI
Input Power 208-240V, 60Hz, 20 Amp, 3 phase
Configuration Indoor, Non-Refrigerated, Water-cooled
   

 


HEATERS, AIR-COOLED RADIATOR STYLE

 
These, useful for engine and component testing offer the unique advantage of no refrigeration and no water use. The units are built with internal heaters to maintain an elevated temperature around 100°C, then cooling is simply performed by turning on a fan, cooling the built-in radiator.
   
   
1HT10P Specs :
 
Temperature Range
+25°C to +130°C
Number of Channels 1
Cooling Capacity

3,000 Watts @ +70°C Fluid Temp.

Heating Capacity

3,000 Watts

Fluid (HTF) 50/50 Ethylene Glycol/Water
Reservoir Volume 7 Gallons
Pump: Flow at Pressure 10 GPM at 20 PSI
Input Power 208-230V, 60Hz, 30 Amp, single-phase