Mydax recirculating liquid chillers: About us, News, Frequently Asked Questions, Contact usTECHNICAL SERVICE SUPPORT for Mydax Chillers: Service-Warranty Options, Technical InformationAPPLICATIONS for Mydax Chillers: Pharmaceutical, Semiconductor, Aerospace, Automotive, Medical, Laser, Industrial, Biotech, Cryogenic. Prototype, Custom, OEM.Mydax PRODUCTS Chiller:  Very Low Temperature, Wide Temperature, Outdoor Air Cooled, Air Cooled, Water Cooled, Liquid to Liquid or Air Heat Exchanger, Precision Air Conditioner, Custom, Deionization Chelating FiltersSALES Mydax chillers: Design your Chiller, Computer Control, Engineering, Request a Quote
 
home | email 
Products
VLH Wide Temp
Outdoor Rated
Air-Cooled
Water-Cooled
Heat Exchangers
Extreme Custom
Multi-Channel
Filters

 

Mydax Non Refrigerated Heat Exchanger Temperature Control Products

MYDAX NON-REFRIGERATED, HEAT EXCHANGER PRODUCTS:

These Heat Exchangers are used when a source of building chiller water or facilities water is already available AND it is at least 5°C colder than your desired coolant temperature.

They provide a closed-loop recirculation system with a clean or pure fluid (like deionized water), and far superior temperature stability.

Read more in our description of the: Heat Exchanger Functional Description.

Mydax Heat Exchangers are most commonly recommended when one or more of the following are required:
Mydax
Precision temperature stability
Mydax
Special custom controls
Mydax
Special fluid handling (materials, pumps, filtration)
Mydax
High reliability
Cooling without refrigeration system

This product is available in the following configurations:
  • Multi-Loop: 1, 2, and 3 independent channels
Special Heat Transfer Fluid (HTF) could be:
  • Deionized Water, specify conductivity|resistivity
  • Water/Dexcool or Ethylene Glycol 50/50
  • PAO, Royco 602; MIL-PRF-87252
  • Galden and H-Galden by Solvay Solexis (Ausimont)
  • Fluorinert and Novec fluids by 3M
Please fill out a Request For Quote Form or email: sales@mydax.com
 
 
 
 
 

In the Chart below, click on any of the models to see a summary of the specifications. From there, you'll be able to download the corresponding PDF datasheet to a new window.
Please Note: These are example systems that can be customized to meet your specific needs.


  Mydax Heat Exchanger Products 1HT10P 1HE14W 1HE20WA 1HE30W 1HE52W-PAO 1HE70W 1HE222WB  
 
 
 

HEAT EXCHANGER SERIES - PRODUCT SUMMARY:

1HT10P Specs :
Temperature Range
+25°C to +130°C
Number of Channels
1
Cooling Capacity
3 KW @ +70°C Fluid Temp
Heating Capacity
3 KW
Temperature Stability
± 1.0 °C or better
Fluid (HTF)
Water / Glycol
Reservoir Volume
7 Gallon
Pump: Flow at Pressure
10 GPM at 20 PSI
Input Power
208/240V, 60Hz, 1ph, 15 Amp
Configuration
Indoor, Non-Refrigerated, Air-cooled
1HE14W Specs :
Temperature Range
+25°C to +90°C
Number of Channels
1
Cooling Capacity
4 KW at +4°C deltaT
Heating Capacity
3 KW
Temperature Stability
± 1.0 °C or better
Fluid (HTF)
Water / Glycol
Reservoir Volume
15 Gallons
Pump: Flow at Pressure
35 GPM at 30 PSI
Input Power
208/240V, 60Hz, 3ph, 40 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
1HE20WA Specs :
Temperature Range
+10°C to +30°C
Number of Channels
1
Cooling Capacity
5.8 KW at +5°C deltaT
Heating Capacity
-
Temperature Stability
± 0.5 °C or better
Fluid (HTF)
High Resistivity Deionized Water
Reservoir Volume
6 Gallons
Pump: Flow at Pressure
4 GPM at 60 PSI
Input Power
208/240V, 60Hz, 3ph, 15 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
1HE30W Specs :
Temperature Range
+10°C to +30°C
Number of Channels
1
Cooling Capacity
8.8 KW at +5°C deltaT
Heating Capacity
-
Temperature Stability
± 0.5 °C or better
Fluid (HTF)
High Resistivity Deionized Water
Reservoir Volume
6 Gallons
Pump: Flow at Pressure
5 GPM at 60 PSI
Input Power
208/240V, 60Hz, 1ph, 10 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
1HE52W-PAO Specs :
Temperature Range
+15°C to +70°C
Number of Channels
1
Cooling Capacity
15 KW at +5°C deltaT
Heating Capacity
3 KW
Temperature Stability
± 1.0 °C or better
Fluid (HTF)
PAO (Royco 602)
Reservoir Volume
6 Gallons
Pump: Flow at Pressure
6 GPM at 55 PSI
Input Power
208/240V, 60Hz, 3ph, 20 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
1HE70W Specs :
Temperature Range
+10°C to +30°C
Number of Channels
1
Cooling Capacity
20 KW at +5°C deltaT
Heating Capacity
-
Temperature Stability
± 2.0 °C or better
Fluid (HTF)
PAO (Royco 602)
Reservoir Volume
18 Gallons
Pump: Flow at Pressure
25 GPM at 120 PSI
Input Power
208/230V, 60Hz, 3 ph, 30 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
1HE222WB Specs :
Temperature Range
+10°C to +30°C
Number of Channels
1
Cooling Capacity
65 KW at +5°C deltaT
Heating Capacity
-
Temperature Stability
± 0.5 °C or better
Fluid (HTF)
High Resistivity Deionized Water
Reservoir Volume
6 Gallons
Pump: Flow at Pressure
10 GPM at 60 PSI
Input Power
208/240V, 60Hz, 3ph, 15 Amp
Configuration
Indoor, Non-Refrigerated, Water-cooled
 
 