MYDAX NON-REFRIGERATED, HEAT EXCHANGER PRODUCTS:
These Heat Exchangers are used when a source of building
chiller water or facilities water is already available AND
it is at least 5°C colder than your desired coolant
temperature.
They provide a closed-loop recirculation system with a clean
or pure fluid (like deionized water), and far superior temperature
stability.
Read more in our description of the: Heat
Exchanger Functional Description.
Mydax Heat Exchangers are most
commonly recommended when one or more of the following
are required:
|
|
|
Precision temperature stability |
|
|
Special custom controls
|
|
|
Special fluid handling (materials,
pumps, filtration)
|
|
High reliability |
|
Cooling without refrigeration system |
This product is available in the following
configurations:
|
|
- Multi-Loop: 1, 2, and 3 independent channels
|
|
|
Special Heat Transfer Fluid (HTF) could
be:
|
|
- Deionized Water, specify conductivity|resistivity
|
|
- Water/Dexcool or Ethylene Glycol 50/50
|
|
- PAO, Royco 602; MIL-PRF-87252
|
|
- Galden and H-Galden by Solvay Solexis (Ausimont)
|
|
- Fluorinert and Novec fluids by 3M
|
|
|
|
|
| |
|
|
| |
In the Chart below, click on any of the models to see
a summary of the specifications. From there, you'll be
able to download the corresponding PDF datasheet
to a new window.
Please Note: These are example systems that can be customized to meet your specific needs.
|
| |
|
|
| |
|
|
| |
HEAT
EXCHANGER SERIES
- PRODUCT SUMMARY:
1HT10P
Specs :
|
|
|
Temperature Range |
+25°C to +130°C |
Number of Channels |
1 |
Cooling Capacity |
3 KW @ +70°C
Fluid Temp
|
Heating Capacity |
3 KW
|
Temperature Stability |
± 1.0 °C or better |
Fluid (HTF) |
Water / Glycol |
Reservoir Volume |
7 Gallon |
Pump: Flow at Pressure |
10 GPM at 20 PSI |
Input Power |
208/240V, 60Hz, 1ph, 15 Amp |
Configuration |
Indoor, Non-Refrigerated, Air-cooled |
|
|
|
|
1HE14W
Specs :
|
|
|
Temperature Range |
+25°C to +90°C |
Number of Channels |
1 |
Cooling Capacity |
4 KW at
+4°C
deltaT
|
Heating Capacity |
3 KW
|
Temperature Stability |
± 1.0 °C or better |
Fluid (HTF) |
Water / Glycol |
Reservoir Volume |
15 Gallons |
Pump: Flow at Pressure |
35 GPM at 30 PSI |
Input Power |
208/240V, 60Hz, 3ph, 40 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
1HE20WA Specs
:
|
|
|
Temperature Range |
+10°C to +30°C |
Number of Channels |
1 |
Cooling Capacity |
5.8 KW at +5°C
deltaT
|
Heating Capacity |
-
|
Temperature Stability |
± 0.5 °C or better |
Fluid (HTF) |
High Resistivity Deionized Water |
Reservoir Volume |
6 Gallons |
Pump: Flow at Pressure |
4 GPM at 60 PSI |
Input Power |
208/240V, 60Hz, 3ph, 15 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
1HE30W Specs : |
|
|
Temperature Range |
+10°C to +30°C |
Number of Channels |
1 |
Cooling Capacity |
8.8 KW at +5°C deltaT |
Heating Capacity |
- |
Temperature Stability |
± 0.5 °C or better |
Fluid (HTF) |
High Resistivity Deionized Water |
Reservoir Volume |
6 Gallons |
Pump: Flow at Pressure |
5 GPM at 60 PSI |
Input Power |
208/240V, 60Hz, 1ph, 10 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
1HE52W-PAO Specs : |
|
|
Temperature Range |
+15°C to +70°C |
Number of Channels |
1 |
Cooling Capacity |
15 KW at +5°C deltaT |
Heating Capacity |
3 KW |
Temperature Stability |
± 1.0 °C or better |
Fluid (HTF) |
PAO (Royco 602) |
Reservoir Volume |
6 Gallons |
Pump: Flow at Pressure |
6 GPM at 55 PSI |
Input Power |
208/240V, 60Hz, 3ph, 20 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
1HE70W Specs : |
|
|
Temperature Range |
+10°C to +30°C |
Number of Channels |
1 |
Cooling Capacity |
20 KW at +5°C deltaT |
Heating Capacity |
- |
Temperature Stability |
± 2.0 °C or better |
Fluid (HTF) |
PAO (Royco 602) |
Reservoir Volume |
18 Gallons |
Pump: Flow at Pressure |
25 GPM at 120 PSI |
Input Power |
208/230V, 60Hz, 3 ph, 30 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
1HE222WB Specs : |
|
|
Temperature Range |
+10°C to +30°C |
Number of Channels |
1 |
Cooling Capacity |
65 KW at +5°C deltaT |
Heating Capacity |
- |
Temperature Stability |
± 0.5 °C or better |
Fluid (HTF) |
High Resistivity Deionized Water |
Reservoir Volume |
6 Gallons |
Pump: Flow at Pressure |
10 GPM at 60 PSI |
Input Power |
208/240V, 60Hz, 3ph, 15 Amp |
Configuration |
Indoor, Non-Refrigerated, Water-cooled |
|
|
|
|
|
|
| |

Advanced Temperature Control Technology

|
home |
support |
applications |
products |
sales|