NON-REFRIGERATED, HEAT EXCHANGER PRODUCTS:
These Heat Exchangers are used when a source of building
chiller water or facilities water is already available AND
it is at least 5°C colder than your desired coolant
temperature.
They provide a closed-loop recirculation system with a clean
or pure fluid (like deionized water), and far superior temperature
stability.
Read more in our description of the: Heat
Exchanger Functional Description.
Mydax Heat Exchangers are most
commonly recommended when one or more of the following
are required:
|
|
|
precision temperature stability
|
|
|
special custom controls
|
|
|
special fluid handling (materials,
pumps, filtration)
|
|
high reliability |
|
both heating and cooling |
This product is available in the following
configurations:
|
| |
- Multi-Loop: 1, 2, and 3 independent channels
|
| |
|
Special Heat Transfer Fluid (HTF) could
be:
|
| |
- Deionized Water, specify conductivity|resistivity
|
| |
- Water/Dexcool or Ethylene Glycol 50/50
|
| |
- PAO, Royco 602; MIL-PRF-87252
|
| |
- Galden and H-Galden by Solvay Solexis (Ausimont)
|
| |
- Fluorinert and Novec fluids by 3M
|
| |
|
|
|
| |
|
|
| |
In the Chart below, click on any of the models to see
a summary of the specifications. From there, you'll be
able to download the corresponding PDF datasheet
to a new window (approx. 1Mb in size, each).
|
|
| |
|
|
| |
|
|
| |
HEAT
EXCHANGER SERIES
- PRODUCT SUMMARY:
1HE20WA
Specs :
|
|
|
| Temperature Range |
+15°C to +30°C
|
| Number of Channels |
1 |
| Cooling Capacity |
5,856 Watts (20,000 Btu/Hr) @ +5°C
deltaT
|
| Heating Capacity |
-
|
| Fluid (HTF) |
Deionized Water |
Optional: |
PAO |
| Reservoir Volume |
6 Gallon |
| Pump: Flow at Pressure |
5 GPM at 60 PSI |
| Input Power |
208-240V, 60Hz, 15 Amp, single-phase |
| Configuration |
Indoor, Non-Refrigerated, Water-cooled |
| |
|
| |
|
1HE222WB
Specs :
|
|
|
| Temperature Range |
+10°C to +30°C
|
| Number of Channels |
1 |
| Cooling Capacity |
65,000 Watts (222,000 Btu/Hr) @
+4°C
deltaT
|
| Heating Capacity |
-
|
| Fluid (HTF) |
Deionized Water |
| Reservoir Volume |
6 Gallons |
| Pump: Flow at Pressure |
10 GPM at 60 PSI |
| Input Power |
208-240V, 60Hz, 15 Amp |
| Configuration |
Indoor, Non-Refrigerated, Water-cooled |
| |
|
| |
|
1HE240W Specs
:
|
|
|
| Temperature Range |
+12°C to +25°C
|
| Number of Channels |
1 |
| Cooling Capacity |
70,275 Watts (240,000 Btu/Hr) @ +7.2°C
(13°F) deltaT
|
| Heating Capacity |
-
|
| Fluid (HTF) |
High Resistivity Deionized Water (1M-3M
Ohm) |
| Reservoir Volume |
42 Gallons |
| Pump: Flow at Pressure |
60 GPM at 60 PSI |
| Input Power |
208-240V, 60Hz, 20 Amp, 3 phase |
| Configuration |
Indoor, Non-Refrigerated, Water-cooled |
| |
|
HEATERS, AIR-COOLED
RADIATOR STYLE |
| |
| These, useful for engine and component
testing offer the unique advantage of no refrigeration
and no water use. The units are built with internal
heaters to maintain an elevated temperature around
100°C, then cooling is simply performed by turning
on a fan, cooling the built-in radiator. |
| |
|
| |
|
1HT10P
Specs :
|
|
|
| Temperature Range |
+25°C to +130°C
|
| Number of Channels |
1 |
| Cooling Capacity |
3,000 Watts @ +70°C Fluid Temp.
|
| Heating Capacity |
3,000 Watts
|
| Fluid (HTF) |
50/50 Ethylene Glycol/Water |
| Reservoir Volume |
7 Gallons |
| Pump: Flow at Pressure |
10 GPM at 20 PSI |
| Input Power |
208-230V, 60Hz, 30 Amp, single-phase |
| Configuration |
Indoor, Non-Refrigerated, Air-cooled |
| |
|
| |
|
|
|
| |