Mydax recirculating liquid chillers: About us, News, Frequently Asked Questions, Contact usTECHNICAL SERVICE SUPPORT for Mydax Chillers: Service-Warranty Options, Technical InformationAPPLICATIONS for Mydax Chillers: Pharmaceutical, Semiconductor, Aerospace, Automotive, Medical, Laser, Industrial, Biotech, Cryogenic. Prototype, Custom, OEM.Mydax PRODUCTS Chiller:  Very Low Temperature, Wide Temperature, Outdoor Air Cooled, Air Cooled, Water Cooled, Liquid to Liquid or Air Heat Exchanger, Precision Air Conditioner, Custom, Deionization Chelating FiltersSALES Mydax chillers: Design your Chiller, Computer Control, Engineering, Request a Quote
 
home | email 
Products
VLH Wide Temp
Outdoor Rated
Air-Cooled
Water-Cooled
Heat Exchangers
Precision Air
Extreme Custom
Multi-Channel
Filters

 

WATER-COOLED PRODUCTS:

A Water-Cooled chiller is generally the least expensive option, while being space saving and efficient when a source of water is available for cooling the condenser. These are designed as indoor units; heat rejected by the refrigeration system goes to the building chiller or facilities water.

Additional wide-temperature (-70°C to +150°C) water-cooled chillers are shown separately under the: VLH Wide-Temp menu.

Mydax Water-Cooled chillers are most often recommended when one or more of the following are required:
precision temperature stability
special custom controls
special fluid handling (materials, pumps, filtration)
high reliability
both heating and cooling

This product is available in the following configurations:
 
  • Multi-Loop: 1, 2, and 3 independent channels
   
Special Heat Transfer Fluid (HTF) could be:
 
  • Galden and H-Galden by Solvay Solexis (Ausimont)
 
  • Fluorinert and Novec fluids by 3M
 
  • Syltherm HF, XLT by DOW Chemical
 
  • Deionized Water, specify conductivity|resistivity
 
  • Deuterium Oxide
   
 
 
 
 

In the Chart below, click on any of the models to see a summary of the specifications. From there, you'll be able to download the corresponding PDF datasheet to a new window (approx. 1Mb in size, each).

 
  Go to VLH Series Low Temperature Chillers  
 
 
 

WATER-COOLED SERIES - PRODUCT SUMMARY:

1M12WB Specs :
Temperature Range
+13°C to +40°C
Number of Channels 1
Cooling Capacity

3,500 Watts (12,000 Btu/Hr) @ +13°C fluid

Heating Capacity

-

Fluid (HTF) Deuterium Oxide (D2O)
Reservoir Volume 1 Gallon
Pump: Flow at Pressure 1.5 GPM at 120 PSI
Input Power 208-240V, 60Hz, 30 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1M13W Specs :
[PDF Datasheet]
Temperature Range
+8°C to +40°C
Number of Channels 1
Cooling Capacity

3,800 Watts (13,000 Btu/Hr) @ +8°C fluid

Heating Capacity

1,000 Watts

Fluid (HTF) Deionized Water (250K-2M Ohms)
Reservoir Volume 7 Gallons
Pump: Flow at Pressure 5 GPM at 90 PSI
Input Power 208-240V, 60Hz, 20 Amp, 3-phase
Configuration Indoor, Water-cooled
   
   
2M30W Specs :
[PDF Datasheet]
Temperature Range
+10°C to +60°C
Number of Channels 2
Cooling Capacity, each

4,400 Watts (15,000 Btu/Hr) @ +10°C fluid

Heating Capacity, each

4,500 Watts

Fluid (HTF) 50/50 Ethylene Glycol/Water or DI water
Reservoir Volume, each 9 Gallons
Pump: Flow at Pressure 15 GPM at 60 PSI and 5 GPM at 110 PSI
Input Power 208-240V, 60Hz, 25 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1M56W Specs :
[PDF Datasheet]
Temperature Range
+8°C to +40°C
Number of Channels 1
Cooling Capacity

16,400 Watts (56,000 Btu/Hr) @ +8°C fluid

Heating Capacity

3,000 Watts

Fluid (HTF) Deionized Water, 300K Ohm
Reservoir Volume 44 Gallons
Pump: Flow at Pressure 25 GPM at 60 PSI
Input Power 440-480V, 60Hz, 30 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1M150W Specs :
[PDF Datasheet]
Temperature Range
+8°C to +40°C
Number of Channels 1
Cooling Capacity

44,000 Watts (150,000 Btu/Hr) @ +20°C fluid

Heating Capacity

3,000 Watts

Fluid (HTF) Deionized Water, 300K Ohm
Reservoir Volume 44 Gallons
Pump: Flow at Pressure 40 GPM at 50 PSI
Input Power 440-480V, 60Hz, 40 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1FT20W Specs :
[PDF Datasheet]
FLOW-THROUGH CHILLER  
Temperature Range
15°C to +25°C
Number of Channels 1
Cooling Capacity

5,856 Watts (20,000 Btu/Hr) @ 7°C deltaT

Fluid 1 (Recirculating)

Water

Fluid 2 (HTF) Deionized Water, 1M Ohm
Reservoir Volume, each 20 Gallons
Pump: Flow at Pressure up to 3 GPM; max pressure drop 2 PSI
Input Power 208-240V, 60Hz, 20 Amp, single-phase
Configuration Indoor, Water-cooled
   
   
1L6W Specs :
[PDF Datasheet]
Temperature Range
-25°C to +20°C
Number of Channels 1
Cooling Capacity

1,760 Watts (6,000 Btu/Hr) @ -20°C fluid

Heating Capacity

-

Fluid (HTF) Methanol
Reservoir Volume 5 Gallons
Pump: Flow at Pressure 5 GPM at 30 PSI
Input Power 208-240V, 60Hz, 30 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
2LH8W Specs :
[PDF Datasheet]
Temperature Range
-25°C to +80°C
Number of Channels 2
Cooling Capacity, each

1,170 Watts (4,000 Btu/Hr) @ -25°C fluid

Heating Capacity, each

1,500 Watts

Fluid (HTF) Galden HT-100
or
50/50 Ethylene Glycol/Water
Reservoir Volume, each 9 Gallons
Pump: Flow at Pressure 10 GPM at 60 PSI
Input Power 208-240V, 60Hz, 50 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1H10W Specs :
[PDF Datasheet]
Temperature Range
+25°C to +150°C
Number of Channels 1
Cooling Capacity

2,900 Watts (10,000 Btu/Hr) @ +25°C fluid

Heating Capacity

3,000 Watts

Fluid (HTF) Turbine Oil, Mineral Oil, SAE 5W Castrol Oil
Reservoir Volume 10 Gallons
Pump: Flow at Pressure 6 GPM at 50 PSI
Input Power 208-240V, 60Hz, 30 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1LH24W Specs :
[PDF Datasheet]
Temperature Range
-10°C to +70°C
Number of Channels 1
Cooling Capacity

7,000 Watts (24,000 Btu/Hr) @ -10°C fluid

Heating Capacity

2,500 Watts

Fluid (HTF) Ethylene Glycol/Water or Fluorinert FC-77
Reservoir Volume 5 Gallons
Pump: Flow at Pressure 9 GPM at 50 PSI or 15 GPM at 50 PSI
Input Power 208-240V, 60Hz, 40 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1H52W Specs :
[PDF Datasheet]
Temperature Range
+20°C to +90°C
Number of Channels 1
Cooling Capacity

15,250 Watts (52,000 Btu/Hr) @ +20°C fluid

Heating Capacity

15,000 Watts

Fluid (HTF) 50/50 Ethylene Glycol/Water
Reservoir Volume 11 Gallons
Pump: Flow at Pressure 10 GPM at 50 PSI
Input Power 208-240V, 60Hz, 70 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
1H100W Specs :
[PDF Datasheet]
Temperature Range
+25°C to +150°C
Number of Channels 1
Cooling Capacity

29,000 Watts (100,000 Btu/Hr) @ +25°C fluid

Heating Capacity

3,000 Watts

Fluid (HTF) Turbine Oil, Mineral Oil, SAE 5W Castrol Oil
Reservoir Volume 10 Gallons
Pump: Flow at Pressure 6 GPM at 50 PSI
Input Power 208-240V, 60Hz, 50 Amp, 3 phase
Configuration Indoor, Water-cooled
   
   
 
 


Advanced Temperature Control Technology

home | support | applications | products | sales| contact